Skip to product information

E2S: D1xB2X05 / D1xB2X10 / D1xB2X15 / D1xB2X21

CI D1 explosion-proof xenon beacon - 20.44cd at 5J, 69.81cd at 10J, 98.61cd at 15J, 215.85cd at 21J, UL1638, 24Vdc

Accreditation
Accreditation image Accreditation image Accreditation image Accreditation image
Coding

D1xB2X05

NEC Class / Zone
Class I Zone 1 AEx db IIC T4 Ta -55°C to +80°C (T5: +75°C)
Class I Zone 1 AEx db IIC T6 Ta -55°C to +60°C (DC only)
Zone 21 AEx tb IIIC T99°C Ta -55°C to +80°C

CEC Class / Zone
Ex db IIC T4 Ta -55°C to +80°C (T5: +75°C, T6: +60°C)
Ex tb IIIC T99°C Ta -55°C to +80°C

NEC / CEC Class / Div
Class I Div 1 Group ABCD T5 Ta -55°C to +80°C (T6: +70°C)
Class II Div 1 Group EFG T5 Ta -55°C to +80°C


D1xB2X10

NEC Class / Zone
Class I Zone 1 AEx db IIC T4 Ta -55°C to +80°C (AC: +65°C)
Class I Zone 1 AEx db IIC T5 Ta -55°C to +45°C
Zone 21 AEx tb IIIC T132°C Ta -55°C to +80°C (AC: T153°C +70°C)

CEC Class / Zone
Ex db IIC T4 Ta -55°C to +80°C (AC: +65°C) T5 to +45°C
Ex tb IIIC T132°C Ta -55°C to +80°C (AC: T153°C +70°C)

NEC / CEC Class / Div
Class I Div 1 Group ABCD T4 Ta -55°C to +80°C (AC: +70°C)
Class I Div 1 Group ABCD T4A Ta -55°C to +70°C (AC: +55°C)
Class I Div 1 Group ABCD T5 Ta -55°C to +50°C
Class II Div 1 Group EFG T4 Ta -55°C to +80°C (AC: +40°C)


D1xB2X15

NEC Class / Zone
Class I Zone 1 AEx db IIC T3 Ta -55°C to +80°C (AC: +65°C)
Class I Zone 1 AEx db IIC T4 Ta -55°C to +65°C
Zone 21 AEx tb IIIC T132°C Ta -55°C to +80°C (AC: T153°C
+70°C)

CEC Class / Zone
Ex db IIC T3 Ta -55°C to +80°C (AC: +70°C)
Ex db IIC T4 Ta -55°C to +65°C
Ex tb IIIC T132°C Ta -55°C to +80°C (AC: T153°C +70°C)

NEC / CEC Class / Div
Class I Div 1 Group ABCD T3C Ta -55°C to +80°C (DC only)
Class I Div 1 Group ABCD T4 Ta -55°C to +55°C (AC: T4A
+55°C)
Class II Div 1 Group EFG T4 Ta -55°C to +80°C (AC: +40°C)
Class III Div 1 Ta -55°C to +80°C (AC: +40°C)


D1xB2X21

NEC Class / Zone
Class I Zone 1 AEx db IIC T3 Ta -55°C to +80°C (AC: +60°C)
Class I Zone 1 AEx db IIC T4 Ta -55°C to +45°C (AC +50°C)
Zone 21 AEx tb IIIC T181°C Ta -55°C to +80°C (AC: T153°C
+60°C)

CEC Class / Zone
Ex db IIC T3 Ta -55°C to +80°C (AC: +60°C)
Ex db IIC T4 Ta -55°C to +45°C (AC: +50°C)
Ex tb IIIC T181°C Ta -55°C to +80°C (AC: T153°C +60°C)

NEC / CEC Class / Div
Class I Div 1 Group ABCD T3B Ta -55°C to +80°C (DC only)
Class I Div 1 Group ABCD T3C Ta -55°C to +75°C (AC: +60°C)
Class I Div 1 Group ABCD T4 Ta -55°C to +50°C (AC: T4 +55°C)
Class II Div 1 Group EFG T3C Ta -55°C to +40°C (AC: T4)
Class III Div 1 Ta -55°C to +80°C (AC: +40°C)

Approvals

Videos

More from this collection

E2S: D1xB2X05 / D1xB2X10 / D1xB2X15 / D1xB2X21

CI D1 explosion-proof xenon beacon - 20.44cd at 5J, 69.81cd at 10J, 98.61cd at 15J, 215.85cd at 21J, UL1638, 24Vdc

Description

The D1xB2X05, D1xB2X10, D1xB2X15, and D1xB2X21 are globally approved explosion-proof Xenon beacons, available in 5 Joule, 10 Joule, 15 Joule, and 21 Joule versions respectively. The robust Type 4/4X, IP66, corrosion-proof LM6 marine grade aluminum alloy enclosure ensures suitability for Class I & II Div 1, Zone 1, 2, 21 & 22 hazardous location applications.

Approved to UL1638 and CAN/ULC S526 for fire alarm use (EN54-23, MED and MER on select models), these beacons produce a high-output Xenon flash for effective visual signaling, including environments with elevated ambient light levels (higher Joule models). The field-replaceable color filter enhances the strobe output and is constructed from UV-stable polycarbonate.

The robust enclosure features a threaded flame path and multiple cable entries (model dependent). Mounting options include surface installation via integrated lugs, pendant mounting, or multi-directional mounting with an optional stainless steel bracket.

SIL1 and SIL2 compliant to IEC 61508 (2010) as standard (Route 2H on select models), with an optional diagnostic module available for Route 1H SIL2 compliance.

Features

D1xB2X05 / D1xB2X10 / D1xB2X15 / D1xB2X21

  • Four selectable flash rates: 1Hz, 1.3Hz, 1.5Hz, and double flash
  • Automatic synchronization on multi-beacon systems
  • A4 316 stainless steel guard included as standard
  • UV-stable polycarbonate lens color filter – field replaceable
  • Corrosion-proof marine grade aluminum enclosure
  • UL 1638 & CAN/ULC S526 listed – Signaling Device for Fire Alarm
  • UL Marine approved
  • Multiple cable entries (4 x side, 1 x pendant on select models) with stopping plugs included
  • EN54-23 tested, UK & EU CPR compliant (model dependent)
  • Manufacturer warranty: 10 years
Approvals
Select product and buy
PART NUMBER: D1XB2X05DC024MN1A1R/A
Quantity
Sale price  $ 1,416.51 Regular price  $ 1,997.78
Description

The D1xB2X05, D1xB2X10, D1xB2X15, and D1xB2X21 are globally approved explosion-proof Xenon beacons, available in 5 Joule, 10 Joule, 15 Joule, and 21 Joule versions respectively. The robust Type 4/4X, IP66, corrosion-proof LM6 marine grade aluminum alloy enclosure ensures suitability for Class I & II Div 1, Zone 1, 2, 21 & 22 hazardous location applications.

Approved to UL1638 and CAN/ULC S526 for fire alarm use (EN54-23, MED and MER on select models), these beacons produce a high-output Xenon flash for effective visual signaling, including environments with elevated ambient light levels (higher Joule models). The field-replaceable color filter enhances the strobe output and is constructed from UV-stable polycarbonate.

The robust enclosure features a threaded flame path and multiple cable entries (model dependent). Mounting options include surface installation via integrated lugs, pendant mounting, or multi-directional mounting with an optional stainless steel bracket.

SIL1 and SIL2 compliant to IEC 61508 (2010) as standard (Route 2H on select models), with an optional diagnostic module available for Route 1H SIL2 compliance.

Features

D1xB2X05 / D1xB2X10 / D1xB2X15 / D1xB2X21

  • Four selectable flash rates: 1Hz, 1.3Hz, 1.5Hz, and double flash
  • Automatic synchronization on multi-beacon systems
  • A4 316 stainless steel guard included as standard
  • UV-stable polycarbonate lens color filter – field replaceable
  • Corrosion-proof marine grade aluminum enclosure
  • UL 1638 & CAN/ULC S526 listed – Signaling Device for Fire Alarm
  • UL Marine approved
  • Multiple cable entries (4 x side, 1 x pendant on select models) with stopping plugs included
  • EN54-23 tested, UK & EU CPR compliant (model dependent)
  • Manufacturer warranty: 10 years

Videos